XM31-915-HP
Power Supply
Alarms
Battery
Log In...
English
Español
Français
Português
Deutsch
Overview
Hardware
Power Supply
Batteries
Environmental I/O
Components
Network
Ethernet
Advanced
Interfaces
Network Services
Diagnostics
Management
System Data
SNMP
Alarms
Utility Power
History
Power Supply Events
Power Supply Configuration
Battery Events
Standby Events
Alarm Log
d
Power Supply
Model
ALPHA/XM31-915-HP
Firmware
V1.07.0
Major Alarm
OK
Minor Alarm
OK
Operational Mode
Line
Charger Mode
Float
Tamper
Door closed
Power Supply Language
English
Power Supply Priority
Normal
d
Input
AC Line Mode
OK
Voltage
122.09
V
Current
5.54
A
Power
570
W
Frequency
60
Hz
Tap Status
Normal
Frequency Range
3.00
Hz
Current Limit
17.00
A
Input Power Consumption
3,787
Wh
1
Output
Voltage
87.01
V
Power
451
W
Apparent Power
502.04
VA
Frequency
60.00
Hz
Percent Load
38.40
%
Output Setting
90 V
Output Regulation
Fine
Over-current Tolerance
3.000
sec
Retry Delay
60
sec
Retry Limit
20
Active Drop Alarm
OK
Active Drop Threshold
50
W
Current
5.77
A
d
Inverter
Inverter Status
Off
End of Discharge Type
String
End of Discharge Level
1.75
V/cell
Reduced Peak Mode
Disable
Total Standby Events
39
Time Since Last Standby Event
16d 3h:54m
Time in Last Standby Event
0d 0h:23m
Total Time in Standby
448
min
Standby Events Since Reset
12
Time in Standby Since Reset
185
min
Time Since Reset
411
day(s)
Total Run Time
411
day(s)
Transformer Run Time
411
day(s)
Total Downtime
0d 0h:10m
Oil Cap Lifespan Consumed
13.8
%
d
Self Test
Deep Discharge Cycle
Timed
Test Countdown
14
day(s)
Test Duration
10
min
Test Interval
30
day(s)
Test Inhibit
No
→ CSV
→ Excel
Copyright © 2017-2025 EnerSys. All Rights Reserved.
www.alpha.com
|
www.enersys.com
Close